35
4.1.3 Keeping Maintenance Records
It is recommended that maintenance operations performed on a detector are recorded in a
Log-book. The record should include the following:
• Installation date, and contractor
• Serial and tag no.
• Entries for every maintenance operation performed, including the description of the
operation, date and personnel ID.
If a unit is sent to Industrial Scientific or a distributor for service, a copy of the
maintenance records should accompany it.
4.2 Troubleshooting
This section is intended to be a guide to correct problems which may happen during
normal operation.
Table 22: Troubleshooting Table
Problem Cause Corrective Action
LEDs Off
Fault Relay at N.O 0-
20mA at 0mA
No power at the unit • Check that the correct power
is sent to the detector.
• Check power polarity.
• Check wiring in the detector.
• Send the detector back for
repairs.
Yellow LED flashes
at 4 Hz
Fault Relay at N.O 0-
20mA at 0mA
Fault Detector
• Low Voltage
• Faulty
Detector
• Check the voltage at the
detector; verify at least 24V
at the detector terminal.
• Send the detector back for
repairs.
Yellow LED flashes
at 4 Hz
Fault Relay at N.O 0-
20mA at 2mA
BIT Fault
• Faulty
Detector
• Clean detector window.
• Re-power the detector.
• Replace the detector.
Red LED constantly
on
If no fire exists, then,
detector alarm
latched
Perform Reset to the detector.
Alarm Relay at On 0-
20mA at 15mA
Alarm condition • Check cause for alarm.
• If no alarm, re-power the
detector.
• Send the detector back for
repairs.